Page 9
Max. cross sections to be connected
Cable end sleeve: 0.25 to 0.75 mm
2
Single-wire 0.50 to 1.50 mm
2
Fine-wired 0.75 to 1.50 mm
2
Interfaces TS1 / TS2 / TS3 / TS4
Design 2 spring-type terminals each
Assignment as inputs
Admissible temperature probe Temperature sensor Pt 1000
Optional assignment of
TS3 / TS4 to the impeller sensor DFZ 1-100 pulses/litre
Optional assignment as
output on TS4 PWM signal 100Hz...2kHz or
analogue output 0...10V, max. 10mA
Triac outputs RO1 / RO2
Design 3 spring-type terminals each, PE, N and L
Output voltage [VAC] 230 ±10%
Output power max.
per output [VA] 200
Output current max.
per output [A] 1
Switching output REL: Floating change-over contact
Design 3 spring-type terminals
Switching voltage max. [V] 253
Switching capacity max. [VA] 230
Switching current max. [A] 1
TECHNICAL DATA