1.3.5 dT control
04. 07. 2015 10:37
Activation dT 1
Activation dT 2
dT 1
dT ON 1
dT OFF 1
2.0k
8.0K
4.0K
PROFESSIONAL MODE
Here, new commissioning
can be started - e. g. if a new
hydraulic system is to be selected.
=> ›Commissioning mode‹ as of page 45.
Continue with ›Delta T control‹.
If control algorithms have been dened as
›dT‹ under ›1.3.7 Output parameter‹, the
appropriate outputs can be congured here.
Via ›dT ON‹, the switch-ON temperature,
via ›dT OFF‹, the switch-OFF temperature
and via ›dT targ.‹, the target differential
temperature are set. (Differential temperature
between collector and tank, bottom).
Continue with ›Fixed T control‹.
Note!
The ›dT targ.1‹ parameter is displayed in the
›1.3.5 dT control‹ menu for systems with 2 collector elds.
With ›dT targ.1‹ the maximum temperature
difference between both collector sensors is specied.
Once this value is exceeded, the pump of the „colder“ collector eld
is deactivated in order to increase efciency.