emz smart Sol - Professional Mode: Commissioning Start; dT Control Algorithm Configuration

emz smart Sol
114 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 95
0 Welcome
04. 07. 2015 10:36
You really want to
start commission.?
YesNo
1.3.5 dT control
04. 07. 2015 10:37
Activation dT 1
Activation dT 2
dT 1
dT ON 1
dT OFF 1
2.0k
8.0K
4.0K
PROFESSIONAL MODE
Here, new commissioning
can be started - e. g. if a new
hydraulic system is to be selected.
=> ›Commissioning mode‹ as of page 45.
Continue with ›Delta T control‹.
If control algorithms have been dened as
›dT‹ under ›1.3.7 Output parameter‹, the
appropriate outputs can be congured here.
Via ›dT ON‹, the switch-ON temperature,
via ›dT OFF‹, the switch-OFF temperature
and via ›dT targ.‹, the target differential
temperature are set. (Differential temperature
between collector and tank, bottom).
Continue with ›Fixed T control‹.
Note!
The ›dT targ.1‹ parameter is displayed in the
›1.3.5 dT control‹ menu for systems with 2 collector elds.
With ›dT targ.1‹ the maximum temperature
difference between both collector sensors is specied.
Once this value is exceeded, the pump of the „colder“ collector eld
is deactivated in order to increase efciency.