Cerabar S
70 Endress+Hauser
Local operation
Remote operation Depending on the position of the write protection switch on the device, all software parameters are accessible.
HART
Remote operation via:
• FieldCare (see "Hardware and software for onsite and remote operation" section → ä 71 ff) with
Commubox FXA195 (see "Hardware and software for onsite and remote operation" section → ä 71 ff)
• Field Xpert SFX100:
Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on Windows
Mobile. It communicates via wireless with the optional VIATOR Bluetooth modem connected to a HART
device point-to-point or wireless via WiFi and Endress+Hauser’s Fieldgate FXA520. Field Xpert also works
as a stand-alone device for asset management applications. For details, refer to BA00060S/04/EN.
PROFIBUS PA
Remote operation via:
• FieldCare (see "Hardware and software for onsite and remote operation" section → ä 71 ff)
– Profiboard: For connecting a PC to PROFIBUS
– Proficard: For connecting a laptop to PROFIBUS
FOUNDATION Fieldbus
Remote operation via:
• Use an FF-configuration program for example NI-FBUS Configurator, to
– connect devices with "FOUNDATION Fieldbus signal" into an FF-network
– set FF-specific parameters
Operation with NI-FBUS Configurator:
The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and a
schedule based on the fieldbus concepts.
You can use the NI-FBUS Configurator to configure a fieldbus network as follows:
– Set block and device tags
– Set device addresses
– Create and edit function block control strategies (function block applications)
– Configure vendor-defined function and transducer blocks
– Create and edit schedules
– Read and write to function block control strategies (function block applications)
– Invoke Device Description (DD) methods
– Display DD menus
– Download a configuration
– Verify a configuration and compare it to a saved configuration
– Monitor a downloaded configuration
Function External operation
(operating keys,
optional, not T17
housing)
Internal operation
(electronic insert)
Display (optional)
Position adjustment
(zero point correction)
XXX
Setting lower-range value
and upper-range value -
reference pressure present at
the device
X
(HART only)
X
(HART only)
X
Device reset X X X
Locking and unlocking
parameters relevant to the
measured value
- - - X
X
Value acceptance indicated
by green LED
XXX
Switching damping on and
off
- - - X
(HART and PA only)
X
Setting bus address (PA) - - - X X
Switching simulation mode
on and off (FOUNDATION
Fieldbus)
- - - X X