Cerabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 23
The following measuring modes are available:
Pressure
Level
5.2.2 Selecting the language and measuring mode via FieldCare
In FieldCare, the MEASURING MODE parameter is displayed in the QUICK Setup menus and
in the BASIC SETUP function group.
The following measuring modes are available:
Pressure
Level
The LANGUAGE parameter is arranged in the DISPLAY group.
Use the LANGUAGE parameter to select the menu language for the onsite display.
Select the menu language for FieldCare using the "Language Button" in the configuration
window. Select the menu language for the FieldCare frame by means of the "Extra" menu È
"Options" "Display" È "Language".
The following languages are available:
•Deutsch
English
Français
•Español
Chinese
Japanese
5.3 Position adjustment
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty or partly filled, the measured value parameter does not display zero. There
are two options to choose from when performing position adjustment.
Onsite display menu path:
GROUP SELECTION OPERATING MENU SETTINGS POSITION ADJUSTMENT
FieldCare menu path:
OPERATING MENU SETTINGS POSITION ADJUSTMENT
In addition, the "Position adjust" method is available if operating by means of a configuration
program.