Cerabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 33
!
Note!
If you have selected the "Direct" mode for the L_TYPE parameter, you cannot change the
values and units for XD_SCALE and OUT_SCALE.
The L_TYPE, XD_SCALE and OUT_SCALE parameters can only be changed in the OOS block
mode.
Make sure that the output scaling of the Pressure Transducer Block SCALE_OUT matches the
input scaling of the Analog Input Block XD_SCALE.