Cerabar T
8 Endress+Hauser
Performance characteristics
Reference operating
conditions
as per DIN IEC 60770, T
U
= 25 °C
Long-term stability ≤ 0.15 % of URL per year
Maximum measured error
of analog output
(under reference operating
conditions)
The measured error comprises the non-linearity including hysteresis and non-reproducibility in accordance
with the limit point method as per IEC 60770.
PMC131
• ≤ 0.5 % of (URL - LRL) x TD
1)
PMP131 and PMP135
• ≤ 0.5 % of URL
Switch point PMP131 and PMP135
• Deviation: ≤ 1 % of URL
• Non-reproducibility: ≤ 0.5 % of URL
Rise time (T90) PMC131
20 ms
Settling time PMP131 and PMP135
2 to 5 ms
1) extended specifications apply to customer-specific measuring ranges
Example: PMC131 version "A1R"
• Nominal value = 10 bar
• Upper range value (URV) = 6 bar
• Lower range value (LRV) = 0 bar
Turn down (is set at factory):
• Nominal value / (URV – LRV)⏐= 10 bar/6 bar = 10:6
P01-PMx13xxx-05-xx-xx-xx-001
Example: PMC131 version "A1R"
set span: 0 to 6 bar; nominal value = 10 bar
1 Span set and calibrated at the factory (measuring
range)
2 Nominal value i Upper Range Limit (URL)
3 Sensor measuring range
LRL Lower Range Limit
URL Upper Range Limit
LRV Lower Range Value
URV Upper Range Value
0 bar +10 bar
URLURV
LRL = LRV
+6 bar
2
1
3