CM14 Commissioning
19
Parameter Configuration options Description
Operating mode pH (pH sensor)
mV (ORP sensor)
Configures the operating mode.
Unit pH, mV Unit of the physical value.
Format none, one, two Configure the number of decimal places for the
display.
Damping main value 0 to 60 s
0 s
Configure the damping for the low-pass
filtering of the input signals.
Temp. comp. Automatic,
Manual,
Off
Configures the temperature compensation.
T. comp. cal. off, Linear Configure the temperature compensation for
cell constant calibration.
Ref. temp.
25 °C
Reference temperature
Process check Check the process settings.
Function On, Off Switch on the process check.
Inactive
time
1 to 240 min
60 min
Duration of the process check.
Band
width
1 to 20 %
1 %
Bandwidth for the process check.
Analog outputs Settings for analog outputs.
Current range
4-20 mA
0-20 mA
Current span for analog output.
Out main 0/4 mA Numerical value 0.000 - 99999
2.0 pH
Physical value corresponding to the lower range
limit of the analog output.
Out main 20 mA Numerical value 0.000 - 99999
12 pH
Physical value corresponding to the upper
range limit of the analog output.
Out temp 0/4 mA Numerical value–50 to 250 °C
–5 °C
Temperature corresponding to the measuring
range lower limit of the temperature input.
Out temp 20 mA Numerical value–50 to 250 °C
100 °C
Temperature corresponding to the measuring
range upper limit of the temperature input.
Damping main value 0 to 60 s
0 s
Configure the damping for the low-pass
filtering of the input signals.
Relay 1/2 Settings for the relay outputs.
Function Off, Min limit, Max limit, In band,
Out band, Error
Configure the function of the relay.
Assignment Main, Temp Assign the relay to the main or temperature
input.
Set point Numerical value
0.0
Cannot be configured for function Error (error
message relay).