Commissioning Deltabar FMD71, FMD72
48 Endress+Hauser
Pos. zero adjust (007)
Navigation Setup → Pos. zero adjust
Write permission Operators/Service engineers/Expert
Description Position adjustment – the pressure difference between zero (set point) and the measured
differential pressure need not be known.
Options Confirm
Cancel
Example Measured value = 2.2 mbar (0.033 psi)
You correct the measured value via the "Pos. zero adjust" parameter with the "Confirm"
option. This means that you are assigning the value 0.0 to the pressure present.
Measured value (after pos. zero adjust) = 0.0 mbar
The current value is also corrected.
Factory setting Cancel
9.10 Configuring level measurement
9.10.1 Information on level measurement
You have a choice of two methods for calculating the level: "In pressure" and "In
height". The table in the "Overview of level measurement" section that follows
provides you with an overview of these two measuring tasks.
The limit values are not checked, i.e. the values entered must be appropriate for the
sensor module and the measuring task for the device to be able to measure
correctly.
Customer-specific units are not possible.
There is no unit conversion.
The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure",
"Empty height/Full height" and "Set LRV/Set URV" must be at least 1% apart. The
value will be rejected, and a warning message displayed, if the values are too close
together.