Deltabar S
Endress+Hauser 13
Dynamic behavior:
FOUNDATION Fieldbus
A typical configuration for the macro cycle time (host system) of 1 s results in the following behavior:
Reading cycle
Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control loop)
Acyclic: typical 10/s
Cycle time (update time)
Cyclic: min. 100 ms
Response time
Cyclic: max. 20 ms (for standard bus parameter settings)
Acyclic: typical 100 ms (for standard bus parameter settings)
Damping A damping affects all outputs (output signal, display).
Via onsite display, handheld terminal or PC with operating program, continuous from 0 to 999 s
Additionally for HART and PROFIBUS PA: via DIP switch on the electronic insert, switch position
"on" = set value and "off"
Factory setting: 2 s
Type Measuring cell Dead time (t
1
)
[ms]
Dead time (t
1
) +
Time constant T63 (=t
2
) [ms]
Dead time (t
1
) +
Time constant T90 (=t
3
) [ms]
PMD75 min. 10 mbar (0.15 psi) and 30 mbar (0.45 psi)
100 mbar (1.5 psi)
500 mbar (7.5 psi)
3 bar (45 psi)
16 bar (240 psi)
90 • 540
150
135
130
150
1085
183
149
137
183
max. 10 mbar (0.15 psi) and 30 mbar (0.45 psi)
100 mbar (1.5 psi)
500 mbar (7.5 psi)
3 bar (45 psi)
16 bar (240 psi)
1090 • 1540
1150
1135
1130
1150
2085
1183
1149
1137
1183
PMD70,
FMD76
min. 25 mbar (0.375 psi)
100 mbar (1.5 psi)
500 mbar (7.5 psi)
3 bar (45 psi)
135 • 4835
415
345
245
10855
689
528
298
PMD70,
FMD76
max. 25 mbar (0.375 psi)
100 mbar (1.5 psi)
500 mbar (7.5 psi)
3 bar (45 psi)
1135 • 5835
1415
1345
1245
11855
1689
1528
1298
FMD77,
FMD78
max. Dependent on the diaphragm seal