Deltabar S
Endress+Hauser 7
Level measurement (level,
volume and mass)
Design and operation mode
P01xMD7xxxx-15-xx-xx-xx-000
Level measurement with Deltabar S
1 Level measurement via pressure piping and PMD70
2 Level measurement with FMD76
3 Level measurement with FMD78
h Height (level)
'p Differential pressure
U Density of the media
g Gravitation constant
Your benefits
Choice of three level operating modes.
Volume and mass measurements in any tank shapes by means of a freely programmable characteristic curve.
Choice of diverse level units with automatic unit conversion.
A customized unit can be specified.
Has a wide range of uses, e.g.
for level measurement in tanks with pressure overlay
in the event of foam formation
in tanks with agitators of screen fittings
in the event of liquid gases
for standard level measurement
Communication protocol 4 to 20 mA with HART communication protocol
PROFIBUS PA
The Endress+Hauser devices meet the requirements of the FISCO model.
Due to the low current consumption of 13 mA ± 1 mA, the following number of devices can be operated
on one bus segment if installing as per FISCO:
up to 7 Deltabar S for Ex ia, CSA IS and FM IS applications
up to 27 Deltabar S for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
Further information on PROFIBUS PA can be found in Operating Instructions BA00034S "PROFIBUS DP/
PA: Guidelines for planning and commissioning" and in the PNO Guideline.
FOUNDATION Fieldbus
The Endress+Hauser devices meet the requirements of the FISCO model.
Due to the low current consumption of 15,5 mA ± 1 mA, the following number of devices can be operated
on one bus segment if installing as per FISCO:
up to 6 Deltabar S for Ex ia, CSA IS and FM IS applications
up to 24 Deltabar S for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
Further information on FOUNDATION Fieldbus, such as requirements for bus system components can be
found in Operating Instructions BA00013S "FOUNDATION Fieldbus Overview".
h=
Δp
ρ g
+
+
h