Deltabar S
14 Endress+Hauser
Protocol-specific data HART
PROFIBUS PA
Manufacturer ID 17 (11 hex)
Device Type Code 23 (17 hex)
Device Revision 21 (15 hex) - SW version 02.1y.zz
HART spezification 5
DD Revision • 4 (russian in language selection)
• 3 (netherlands in language selection)
Device description files
(DTM, DD)
Information and files can be found:
• www.endress.com
• www.hartcomm.org
HART load Min. 250 :
HART device variables The measured values can be freely assigned to the device variables:
Measured values for PV (primary variable)
• Pressure
•Flow
• Level
• Tank content
Measured values for SV, TV (second and third variable)
• Pressure
• Totalizer
Measured values for QV (fourth variable)
• Temperature
Supported functions • Burst mode
• Additional Transmitter Status
• Device Locking
• Alternative operating modes
Manufacturer ID 17 (11 hex)
Ident number 1542 hex
Profile Version 3.0
• SW Version 03.00.zz
• SW Version 04.00.zz
3.02
• SW Version 04.01.zz (Device Revision 3)
Compartibility SW version 03.00.zz and higher.
GSD Revision • 4 (SW Version 3.00.zz and 4.00.zz)
•5 (Device Revision 3)
DD Revision • 1 (SW Version 3.00.zz and 4.00.zz)
•1 (Device Revision 3)
GSD File Information and files can be found:
• www.endress.com
• www.profibus.org
DD Files
Output values Measured values for PV (über Analog Input Function Block)
• Pressure
•Flow
• Level
• Tank content
Measured values for SV
• Pressure
• Temperature
Measured values for QV
• Totalizer
Input values Input value sent from PLC, can be shown on display