Installation Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART
20 Endress+Hauser
Installation position for level measurement
Level measurement in an open container
P01-PMD55xxx-11-xx-xx-xx-003
Measuring layout for level measurement in open containers
1 The low-pressure side is open to atmospheric pressure
2Deltabar M
3 Shut-off valve
4 Separator
5 Drain valve
Mount the Deltabar M below the lower measuring connection so that the impulse piping is always
filled with liquid.
The low-pressure side is open to atmospheric pressure.
When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
Level measurement in a closed container
P01-PMD55xxx-11-xx-xx-xx-004
Measuring layout for level measurement in a closed container
1 Shut-off valves
2Deltabar M
3 Separator
4 Drain valves
5 Three-valve manifold
Mount the Deltabar M below the lower measuring connection so that the impulse piping is always
filled with liquid.
Always connect the low-pressure side above the maximum level.
When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
+
p
atm
min.
p
atm
+
min.
max.