Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART Commissioning
Endress+Hauser 51
6 Commissioning
#
Warning!
If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, the following messages are output in succession:
1. "S140 Working range P" or "F140 Working range P"
)
2. "S841 Sensor range" or "F841 Sensor range"
1)
3. "S971 Sensor range"
)
!
Note!
The device is configured for the Pressure measuring mode as standard. The measuring range and
the unit in which the measured value is transmitted correspond to the specifications on the
nameplate.
6.1 Function check
Carry out a post-installation and a post-connection check as per the checklist before commissioning
the device.
"Post-installation check" checklist Chap. 3.8
"Post-connection check" checklist Chap. 4.5
1) depending on the setting in the "Alarm behavior" (050) parameter