Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART Commissioning
Endress+Hauser 69
6.6.3 Semi-automatic entry of the linearization table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m
3
.
Prerequisite:
The tank can be filled or emptied. The linearization characteristic must rise continuously.
The "Level" operating mode has been selected.
!
Note!
For a description of the parameters mentioned Chap. 10.2 "Description of parameters".
Description
1 Select the "Semi-auto. entry" option via the "Lin. mode"
parameter.
Menu path: Setup Extended setup Linearization
Lin. mode
P01-Mxxxxxxx-19-xx-xx-xx-006
2 Select the volume unit/mass unit via the "Unit after lin."
parameter, e.g. m
3
.
Menu path: Setup Extended setup Linearization
Unit after lin.
3 Fill the tank to the height of the 1st point.
3.5
0
03
V
[m ]
3
h
[m]