Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART Commissioning
Endress+Hauser 61
!
Note!
1. The measured variables %, level, volume and mass are available for this level mode. See
ä 114 "Output unit (025)".
5 Select the "Dry" option via the "Calibration mode"
parameter.
Menu path: Setup Extended setup Level
Calibration mode
P01-xxxxxxxx-05-xx-xx-xx-026
P01-xxxxxxxx-05-xx-xx-xx-028
Fig. 30: Calibration with reference pressure –
wet calibration
1 See Table, Step 6.
2 See Table, Step 7.
3 See Table, Step 8.
4 See Table, Step 9.
5 See Table, Step 11.
6 See Table, Step 12.
6 Enter the volume value for the lower calibration point
via the "Empty calib." parameter, here 0 liters for
example.
Menu path: Setup Extended setup Level Empty
calib.
7 Enter the pressure value for the lower calibration point
via the "Empty pressure" parameter, here 50 mbar (0.75
psi) for example.
Menu path: Setup Extended setup Level Empty
pressure
8 Enter the volume value for the upper calibration point
via the "Full calib." parameter, here 1000 liters (264 US
gal) for example.
Menu path: Setup Extended setup Level Full
calib.
9 Enter the pressure value for the upper calibration point
via the "Full pressure" parameter, here 450 mbar (6,75
psi) for example.
Menu path: Setup Extended setup Level Full
pressure
10 "Adjust density" contains the factory setting 1.0 but this
value can be changed if required. The value pairs
subsequently entered must correspond to this density.
Menu path: Setup Extended setup Level Adjust
density
11 Set the volume value for the lower current value (4 mA)
via the "Set LRV" parameter.
Menu path: Setup Extended setup Current output
Set LRV
12 Set the volume value for the upper current value
(20 mA) via the "Set URV" parameter.
Menu path: Setup Extended setup Current output
Set URV
13 If calibration was performed with a medium other than
the process medium, specify the density of the process
medium in the "Process density" parameter.
Menu path: Setup Extended setup Level
Process density
14 Result:
The measuring range is set for 0 to 1000 l (264 US gal).
Description
1000
0
V
[l]
50 450
p
[mbar]
20
4
I
[mA]
0 1000
V
[l]

Table of Contents