Deltapilot M 4...20 mA HART Commissioning
Endress+Hauser 43
7 Enter the pressure value for the lower calibration
point via the "Empty pressure" parameter, here 50
mbar (0.75 psi) for example.
Menu path: Setup Extended setup Level
Empty pressure
A0031028
A0031064
Fig. 13: Calibration with reference pressure –
wet calibration
A See Table, Step 6.
B See Table, Step 7.
C See Table, Step 8.
D See Table, Step 9.
E See Table, Step 11.
F See Table, Step 12.
8 Enter the volume value for the upper calibration
point via the "Full calib." parameter, here 1000 liters
(264 US gal) for example.
Menu path: Setup Extended setup Level
Full calib.
9 Enter the pressure value for the upper calibration
point via the "Full pressure" parameter, here 450
mbar (6,75 psi) for example.
Menu path: Setup Extended setup Level
Full pressure
10 "Adjust density" contains the factory setting 1.0 but
this value can be changed if required. The value
pairs subsequently entered must correspond to this
density.
Menu path: Setup Extended setup Level
Adjust density
11 Set the volume value for the lower current value (4
mA) via the "Set LRV" parameter.
Menu path: Setup Extended setup Current
output Set LRV
12 Set the volume value for the upper current value
(20 mA) via the "Set URV" parameter.
Menu path: Setup Extended setup Current
output Set URV
13 If calibration was performed with a medium other
than the process medium, specify the density of the
process medium in the "Process density" parameter.
Menu path: Setup Extended setup Level
Process density
14 Result:
The measuring range is set for 0 to 1000 l (264 US
gal).
Description
A
B
C
D
V
[l]
p
[mbar]
1000
0
50450
E
F
I
[mA]
V
[l]
20
4
0 1000