Deltapilot M 4...20 mA HART Commissioning
Endress+Hauser 45
Description
1 Perform position adjustment. See ä 37.
A0031027
Fig. 14: Calibration with reference pressure –
wet calibration
A See Table, Step 10.
B See Table, Step 8.
C See Table, Step 9.
2 Select the "Level" measuring mode via the
"Measuring mode" parameter.
Menu path: Setup Measuring mode
3 Select the "In height" level mode via the "Level
selection" parameter.
Menu path: Setup Extended setup Level
Level selection
4 Select a pressure unit via the "Press eng. unit"
parameter, here mbar for example.
Menu path: Setup Press. eng. unit
5 Select a level unit via the "Unit before lin"
parameter, here "l" (liters) for example.
Menu path: Setup Extended setup Level
Unit before lin