Deltapilot S FOUNDATION Fieldbus Commissioning
Endress+Hauser 21
Configuring the Resource Block
1. Open the Resource Block.
2. If necessary, disable the lock for device operation. ä 19, Section 4.4
"Locking/unlocking operation". Operating is unlocked as standard.
3. If necessary, change the block name. Factory setting: RS_452B481007-xxxxxxxxxxx
4. If necessary, assign a description to the block by means of the TAG_DESC parameter.
5. If necessary, change other parameters as per the requirements.
Configuring the Transducer Blocks
Deltapilot S has the following Transducer Blocks:
Pressure Transducer Block
Service Transducer Block
Display Transducer Block
Diagnostic Transducer Block
The explanation that follows is an example for the Pressure Transducer Block.
1. If necessary, change the block name. Factory setting: RS_452B481007-xxxxxxxxxxx
2. Set the block mode to OOS using the MODE_BLK parameter, TARGET element.
3. Configure the device in accordance with the measuring task. See also these Brief
Operating Instructions Section 5.2 to Section 5.6.
4. Set the block mode to Auto using the MODE_BLK parameter, TARGET element.
!
Note!
The block mode must be set to "Auto" for the Pressure and Service Transducer Block for the
measuring device to function correctly.
Configuring the Analog Input Blocks
Deltapilot S has 2 Analog Input Blocks that can be assigned as required to the various process
variables.
1. If necessary, change the block name. Factory setting: RS_452B481007-xxxxxxxxxxx
2. Set the block mode to OOS using the MODE_BLK parameter, TARGET element.
3. Use the CHANNEL parameter to select the process variable which should be used as the
input value for the Analog Input Block. The following settings are possible:
CHANNEL = 1: Primary value, a pressure or level value depending on the measuring
mode selected
CHANNEL = 2: Secondary value, here the sensor temperature
Factory setting:
Analog Input Block 1: CHANNEL = 1: Primary Value (pressure measured value)
Analog Input Block 2: CHANNEL = 2: Secondary Value (sensor temperature)