Endress+Hauser Deltapilot S FMB70 - Connecting the Measuring Unit

Endress+Hauser Deltapilot S FMB70
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Deltapilot S FOUNDATION Fieldbus Wiring
Endress+Hauser 9
P01-xMx7xxxx-04-xx-xx-xx-010
Fig. 3: Electrical connection FOUNDATION Fieldbus. Observe also the following section.
For devices with 7/8" plug see Operating Instructions.
1Housing
2 Internal ground terminal
3 External ground terminal
4 Supply voltage, for version in non-hazardous area = 9 to 32 V DC
5 Devices with integrated overvoltage protection are labeled OVP (overvoltage protection) here.
3.2 Connecting the measuring unit
!
Note!
For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions
BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
3.2.1 Supply voltage
Version for non-hazardous area: 9 to 32 V DC
3.2.2 Current consumption
15.5 mA +/- mA, switch-on current corresponds to IEC 61158-2, Clause 21.
3.2.3 Cable specification
Use a twisted, shielded two-wire cable, preferably cable type A.
Terminals for wire cross-sections: 0.5 to 2.5 mm
2
Outer cable diameter: 5 to 9 mm
!
Note!
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", the FOUNDATION Fieldbus Guideline and IEC 61158-2
(MBP).
FF FF
FF FF
1
2
3
4
5