• Due to the orientation of the Deltapilot S, there may be a shift in the measured value, i.e.
when the container is empty, the measured value does not display zero. You can correct this
zero point shift either via the "zero" key on the electronic insert, or on the outside of the
device or via the onsite display. → ä 13, Section 4.2.1 "Position of operating elements",
→ ä 14, Section 4.2.2 "Function of the operating elements – onsite display not connected"
and → ä 23, Section 5.3 "Position adjustment".
• To ensure optimal readability of the onsite display, it is possible to rotate the housing up to
380°.
• The onsite display can be rotated in 90° stages.
• Endress+Hauser offers a mounting bracket for installing on pipes or walls.
2.2 Measuring arrangement
2.2.1 Level measurement
P01-PMP75xxx-11-xx-xx-xx-000
Fig. 1: Measuring arrangement for level
• Always install the device below the lowest measuring point.
• Do not install the device at the following positions:
– in the filling curtain
– in the tank outflow
– in the suction area of a pump
– or at a point in the tank that can be affected by pressure pulses from the agitator
• The calibration and functional test can be carried out more easily if you mount the device
downstream of a shutoff device.
• Deltapilot S must be included in the insulation for media that can harden when cold.