Installation Deltapilot S FOUNDATION Fieldbus
4 Endress+Hauser
1.5 Safety icons
2 Installation
2.1 General installation instructions
#
Warning!
The seal is not allowed to press on the process isolating diaphragm as this could affect the
measurement result.
!
Note!
If a heated Deltapilot S is cooled during the cleaning (e.g. by cold water), a vacuum develops
for a short time, whereby water can penetrate the sensor through the pressure compensation
(1). If this is the case, mount the sensor with the pressure compensation (1) pointing
downwards.
Keep the pressure compensation and GORE-TEX
®
filter (1) free from contaminations.
Do not use sharp or hard objects to handle or clean the process isolating diaphragm.
Symbol Meaning
#
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury,
a safety hazard or destruction of the instrument.
"
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or
incorrect functioning of the instrument.
!
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation
or may lead to an instrument response which is not planned.