Deltapilot S FOUNDATION Fieldbus Commissioning
Endress+Hauser 31
!
Note!
For local operation see also → ä 14, Section 4.2.3 "Function of the operating elements – onsite
display connected" and → ä 15, Section 4.3 "Onsite operation via onsite display".
Local operation FieldCare
Measured value display
Switch from the measured value display to the GROUP
SELECTION with F.
Measured value display
Select QUICK SETUP menu.
GROUP SELECTION
Select the MEASURING MODE parameter.
Measuring Mode
Select the Primary Value Type parameter.
MEASURING MODE
Select "Pressure".
GROUP SELECTION
Select QUICK SETUP menu.
Primary Value Type
Select "Pressure".
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the
measured value. You correct the MEASURED VALUE via the
POS. ZERO ADJUST parameter with the "Confirm" option,
i.e. you assign the value 0.0 to the pressure present.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the
measured value. You correct the MEASURED VALUE via the
POS. ZERO ADJUST parameter with the "Confirm" option,
i.e. you assign the value 0.0 to the pressure present.
POS. INPUT VALUE
Due to orientation of the device, there may be a shift in the
measured value. For the POS. INPUT VALUE parameter,
specify the desired set point for the MEASURED VALUE.
POS. INPUT VALUE
Due to orientation of the device, there may be a shift in the
measured value. For the POS. INPUT VALUE parameter,
specify the desired set point for the MEASURED VALUE.
DAMPING VALUE
Enter damping time (time constant τ). The damping affects
the speed at which all subsequent elements, such as the
onsite display, measured value and OUT Value of the Analog
Input Block react to a change in the pressure.
DAMPING VALUE
Enter damping time (time constant τ). The damping affects
the speed at which all subsequent elements, such as the
onsite display, measured value and OUT Value of the Analog
Input Block react to a change in the pressure.