Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
148 Endress+Hauser
OUTPUT UNIT (023)
Selection
Select the unit for the measured value display and the MEASURED VALUE parameter
(→ ä 201).
!
Note!
The selected unit is used only to describe the measured value. This means that when
selecting a new output unit, the measured value is not converted.
Example:
• Current measured value: 0.3 ft
• New output unit: m
• New measured value: 0.3 m (9.8 ft)
Options:
•%
• mm, cm, dm, m
•ft, inch
•cm
3
, dm
3
, m
3
,m
3
E
3
•l, hl
•ft
3
, ft
3
E
3
• gal, bbl, Igal
•g, kg, t
• lb, ton, oz
Factory setting:
%
CALIBRATION MODE (008)
Selection
Select the calibration mode.
Options:
•Wet
Wet calibration takes place by filling and emptying the container. In the case of two
different levels, the level, volume, mass or percentage value entered is assigned to the
pressure measured at this point in time. (→ See also this table, parameter descriptions
for EMPTY CALIB. and FULL CALIB.)
•Dry
Dry calibration is a theoretical calibration. For this calibration, you specify two
pressure-level value pairs via the following parameters: EMPTY CALIB., EMPTY
PRESSURE, FULL CALIB. and FULL PRESSURE.
Factory setting:
Wet
EMPTY CALIB. (010)
Entry
Enter the level, volume, mass or percentage value for the lower calibration point (empty
container).
The container is either empty or part full. By entering a value for this parameter, you
assign a level, volume, mass or percentage value to the pressure present at the device.
The unit is selected via the OUTPUT UNIT parameter (→ ä 148).
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the local operation shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
0.0
Table 8: OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL SELECTION "Level easy pressure"
Parameter name Description