Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 165
P01-xMx7xxxx-19-xx-xx-en-007
Fig. 47: BASIC SETUP function group for the "Level" measuring mode and "Pressure linearized" level mode, continue
calibration with LINEARIZATION function group → ä 186 ff.
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the local
operation, measured value and OUT value of the Analog Input Block react to a change in
the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specifications
Table 11: OPERATING MENU → SETTINGS → BASIC SETUP "Level", LEVEL MODE "Linear"
Parameter name Description
*
*
*
*
*
*
*
Linear
Pressure Linearized
Height Linearized
Parameters marked with an asterisk "*"
are not always displayed.Thedisplay
depends on the settings of other parameters,
see the following Table.
Flow
Pressure
Level
PRESS. ENG. UNIT
CUSTOMER UNIT P
CUST. UNIT FACT. P
LEVEL MODE
MEASURING MODE
BASICSETUP
DISPLAYSETTINGS
POSITION ADJUSTMENT
OPERATING MENU
EXTENDED SE TUP
Pressure and ground
Pressure and volume
% ofLevel
MASS UNIT
CUSTOMER UNIT M
CUST. UNIT FACT. M
HYDR. PRESS MIN.
HYDR. PRESS MAX.
DAMPING VALUE
VOLUME UNIT
CUSTOMER UNIT V
CUST. UNIT FACT. V
LINd MEASURAND