Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
166 Endress+Hauser
Table 12: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL MODE "Pressure linearized"
Parameter name Description
The following parameters are displayed if you selected the "Pressure linearized" option for the LEVEL MODE parameter.
For this level mode, the measured variable (volume, mass or %) is not in direct proportion to the measured pressure. For
the calibration, enter a linearization table with at least 2 and not more than 32 points.
Prerequisite:
MEASURING MODE = Level
LEVEL MODE = Pressure linearized ( ä 156).
Note:
See also
ä 155 ff, Table 10: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL SELECTION "Level
standard" – general
ä 183 ff, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 186 ff, Table 18: GROUP SELECTION OPERATING MENU SETTINGS LINEARIZATION – Local
operation and Table 19: MANUFACTURER VIEW OPERATING MENU SETTINGS LINEARIZATION –
FieldCare
ä 201 ff, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level"
ä 105 ff, Section 9 "Level measurement (via local operation and FieldCare)".
LINd. MEASURAND (805)
Selection
Select the measured variable.
Options:
Pressure and volume
Pressure and mass
Pressure and %
Factory setting:
Pressure and %
UNIT VOLUME (313)
Selection
Select the volume unit.
Prerequisite:
LINd. MEASURAND = Pressure and volume
Options:
•l
•hl
•cm
3
•dm
3
•m
3
•m
3
E
3
•ft
•ft
3
E
3
•gal
•Igal
•bbl
•User unit, see also the following parameter descriptions for CUSTOMER UNIT V
and CUST. UNIT. FACT. V
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
m
3