Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 155
Table 10: OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL SELECTION "Level standard"
Parameter name Description
Prerequisite:
• MEASURING MODE = Level
Note:
See also
– → ä 158 ff, Table 11: OPERATING MENU → SETTINGS → BASIC SETUP "Level", LEVEL MODE "Linear" to Table
13: OPERATING MENU → SETTINGS → BASIC SETUP "Level", LEVEL MODE "Height linearized" – contd
– → ä 183 ff, Table 16: OPERATING MENU → SETTINGS → EXTENDED SETUP "Level"
– → ä 186 ff, Table 18: GROUP SELECTION → OPERATING MENU → SETTINGS → LINEARIZATION – Local
operation
– → ä 201 ff, Table 28: OPERATING MENU → PROCESSINFO → PROCESS VALUES "Level"
– → ä 105 ff, Section 9 "Level measurement (via local operation and FieldCare)".
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The digital output
value of the Analog Input Block OUT no longer displays the same value as the local
operation or the MEASURED VALUE. The device has to be recalibrated if the measuring
mode is changed. → ä 105, Section 9 "Level measurement (via local operation and
FieldCare)".
Options:
• Pressure
• Level
• Deltabar S: Flow
Factory setting:
Pressure (Deltabar S, Cerabar S)
Factory setting:
Deltabar S, Cerabar S = Pressure
Deltapilot S = Level easy pressure
PRESS. ENG. UNIT (060)
Selection
Select the pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options:
• mbar, bar
• mmH2O, mH2O, inH2O, ftH2O
• Pa, hPa, kPa, MPa
•psi
• mmHg, inHg
•Torr
•g/cm
2
, kg/cm
2
•lb/ft
2
•atm
•gf/cm
2
, kgf/cm
2
•User unit, → see also the following parameter descriptions for CUSTOMER UNIT P
and CUST. UNIT. FACT. P
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
→ See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
Depends on the sensor nominal measuring range mbar or bar or as per order
specifications