Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
158 Endress+Hauser
Table 11: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL MODE "Linear"
Parameter name Description
The following parameters are displayed if you selected the "Linear" option for the LEVEL MODE parameter. For this level
mode, the measured variable (level, volume, mass or %) is in direct proportion to the measured pressure.
Prerequisite:
MEASURING MODE = Level
LEVEL MODE = Linear ( ä 156)
Note:
See also
ä 155 ff, Table 10: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL SELECTION "Level
standard" – general
ä 183 ff, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 201 ff, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level"
ä 105 ff, Section 9 "Level measurement (via local operation and FieldCare)".
LIN. MEASURAND (804)
Selection
Select the measured variable.
Options:
Level
•Volume
•Mass
% (level)
Factory setting:
% (level)
HEIGHT UNIT (708)
Selection
Select the level unit.
Prerequisite:
LIN. MEASURAND = Level
Options:
•mm
•cm
•dm
•m
•inch
•ft
•User unit, see also the following parameter descriptions for CUSTOMER UNIT H
and CUST. UNIT. FACT. H.
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
m
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST. UNIT. FACT. H.
Prerequisite:
LIN. MEASURAND = Level, HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _