Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
156 Endress+Hauser
CUSTOMER UNIT P (075)
Entry
Enter text (unit) for customer-specific pressure unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT. FACT. P
Prerequisite:
• PRESS. ENG. UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. P (317)
Entry
Enter the conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". → See also
CUSTOMER UNIT P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE =10000 Pa i 1 PU
– Entry CUSTOMER UNIT P: PU
– Entry CUST. UNIT FACT. P: 0.0001
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
LEVEL MODE (718)
Selection
Select level mode.
Options:
• Linear: The measured variable (level, volume, mass or %) is in direct proportion to the
measured pressure. → ä 158 ff, Table 11.
• Pressure linearized: The measured variable (volume, mass or %) is not in direct
proportion to the measured pressure such as in the case of containers with a conical
outlet. For the calibration, enter a linearization table with at least 2 and not more than
32 points. → ä 166 ff, Table 12: OPERATING MENU → SETTINGS → BASIC
SETUP "Level", LEVEL MODE "Pressure linearized".
• Height linearized: Select this level mode if you require two measured variables or if the
container shape is given with value pairs, e.g. height and volume.
The following combinations are possible:
–Height + volume
–Height + mass
–Height + %
– %-height + volume
– %-height + mass
– %-height + %
Perform two calibrations for this level mode. First for the measured variable height or
%-height like for the "Linear" option and then for the measured variable volume, mass
or % like for the "Pressure linearized" option. → ä 170 ff, Table 13: OPERATING
MENU → SETTINGS → BASIC SETUP "Level", LEVEL MODE "Height linearized".
Factory setting:
Linear
→ For LEVEL MODE = Linear, → ä 158 ff, Table 11: OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear".
→ For LEVEL MODE = Pressure linearized, → ä 166 ff, Table 12: OPERATING MENU → SETTINGS → BASIC SETUP
"Level", LEVEL MODE "Pressure linearized".
→ For LEVEL MODE = Height linearized, → ä
170 ff, Table 13: OPERATING MENU → SETTINGS → BASIC SETUP
"Level", LEVEL MODE "Height linearized".
Table 10: OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL SELECTION "Level standard"
Parameter name Description