Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 185
Table 17: OPERATING MENU SETTINGS EXTENDED SETUP "Flow"
Parameter name Description
Prerequisite:
•MEASURING MODE = Flow
Note:
See also ä 129 ff, Section 10 "Flow measurement (via local operation and FieldCare)".
TEMP. ENG. UNIT (318)
Selection
Select the unit for the temperature measured value.
See also PCB TEMPERATURE ( ä 197) and SENSOR TEMP. ( ä 202).
Options:
•°C
•°F
•K
•R
Factory setting:
°C
LOW FLOW CUT-OFF (442)
Selection
Switch the "low flow cut-off" function on and off.
In the lower measuring range, small flow quantities (creepages) can lead to large
fluctuations in the measured value. Switching on this function stops these flow quantities
from being recorded. See also SET. L. FL. CUT-OFF.
Options:
•Off
•On
Factory setting:
Off
SET. L. FL. CUT-OFF (332)
Entry
Enter the switch-off point of low flow cut-off.
The hysteresis between the switch-on point and the switch-off point is always 1 % of the
end flow value. See also LOW FLOW CUT-OFF.
Prerequisite:
LOW FLOW CUT-OFF = On
Input range:
Switch-off point: 0 to 50 % of end flow value (MAX. FLOW).
P01-PMD7xxxx-05-xx-xx-xx-000
Factory setting:
5 % (of end flow value)