Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
202 Endress+Hauser
LEVEL BEFORE LIN (050)
Display
Displays the level value prior to linearization.
Prerequisite:
• LEVEL MODE = Linear or height linearized
Depending on the setting for the LIN. MEASURAND or COMB. MEASURAND
parameter, this parameter displays the current level in % or in a unit of level.
TANK CONTENT (370)
Display
Displays the level value after linearization.
Prerequisite:
• LEVEL MODE = Pressure linearized or height linearized
Depending on the settings for the LINd. MEASURAND or COMB. MEASURAND
parameter, the current tank content is displayed in % or in a unit of volume or mass. This
value corresponds to the MEASURED VALUE.
Table 29: OPERATING MENU → PROCESSINFO → PROCESS VALUES "Flow"
Parameter name Description
Prerequisite:
• MEASURING MODE = Flow
MEASURED VALUE (679)
Display
Displays the measured value
In the "Flow" measuring mode, this value corresponds to the SUPPRESSED FLOW
parameter.
PRESSURE (301)
Display
Displays the measured pressure after sensor recalibration, position adjustment and
damping. This value corresponds to the MEASURED VALUE parameter in the "Pressure"
measuring mode.
P01-xMD7xxxx-05-xx-xx-en-003
CORRECTED PRESS. (434)
Display
Displays the measured pressure after sensor trim and position adjustment and before
damping. → See also PRESSURE diagram.
SENSOR PRESSURE (584)
Display
Displays the measured pressure before sensor trim, position adjustment and damping.
→ See also PRESSURE diagram.
SENSOR TEMP. (367)
Display
Displays the temperature currently measured in the sensor. This can deviate from the
process temperature.
MEAS. VAL. TREND (378)
Display
Displays the trend of the primary value of the Transducer Block.
Possibilities: increasing, decreasing, constant
SUPPRESSED FLOW (375)
Display
Displays the current flow. Depending on the flow mode selected (→ FLOW-MEAS.
TYPE), a volume flow, mass flow, standard volume flow or corrected volume flow is
displayed.
TOTALIZER 1 (652)
Display
Displays the total flow value of totalizer 1. You can reset the value with the RESET
TOTALIZER 1 parameter. The TOTAL. 1 OVERFLOW parameter displays the overflow.
Example: The value 123456789 m
3
is displayed as follows:
– TOTALIZER 1: 3456789 m
3
– TOTAL. 1 OVERFLOW: 12 E7
TOTAL. 1 OVERFLOW (655)
Display
Displays the overflow value of totalizer 1.
→ See also TOTALIZER 1.
TOTALIZER 2 (657)
Display
Displays the total flow value of totalizer 2. You cannot reset totalizer 2. The TOTAL. 2
OVERFLOW parameter displays the overflow.
→ See also example for TOTALIZER 1.
Table 28: OPERATING MENU → PROCESSINFO → PROCESS VALUES "Level"
Parameter name Description
P
PV
Sensor
Analog
Input
Block
Pressure
Level
Flow
PRESSURE
Damping
CORRECTED
PRESS.
Position
adjust-
ment
Sensor
trim
SENSOR
PRESSURE
Transducer Block