Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 203
TOTAL. 2 OVERFLOW (658)
Display
Displays the overflow value of totalizer 2.
See also TOTALIZER 2 and example for TOTALIZER 1.
Table 30: OPERATING MENU PROCESSINFO Function Blocks
Parameter name Description
AI 1 OUT Value (983)
Display
The current values are displayed for instantiated analog inputs, with their individual units
and status.
The first line displays the AI text. The second line displays the current value for the
parameter and the unit. The third line displays the status of the value.
AI 2 OUT Value (982)
Display
The following list indicates the status and the related text of the AI OUT value:
Status Text
AI 3 OUT Value (981)
Display
Bad
Uncertain
Good non-cascaded
Good cascaded
=
=
=
=
BAD
UNCERTAIN
GOOD
GOOD
Note:
When delivered:
Two AI Blocks are preinstantiated for Cerabar S and Deltapilot S
Three AI Blocks are preinstantiated for Deltabar S
Up to three additional AI Blocks are instantiated.
Table 31: OPERATING MENU PROCESSINFO PEAK HOLD INDICATOR
Parameter name Description
COUNTER:P > Pmax (380)
Display
Displays the overpressure counter of the sensor
The limit value is: upper nominal pressure limit of sensor + 10 % of upper nominal
pressure limit of sensor. You can reset this counter by means of the RESET PEAKHOLD
parameter.
MAX. MEAS. PRESS. (383)
Display
Displays the highest measured pressure value (peak hold indicator). You can reset this
indicator by means of the RESET PEAKHOLD parameter.
COUNTER P < Pmin (467)
Display
Displays the vacuum pressure counter of the sensor
The limit value is: lower nominal pressure limit of sensor – 10 % of upper nominal
pressure limit of sensor. You can reset this counter by means of the RESET PEAKHOLD
parameter.
MIN. MEAS. PRESS. (469)
Display
Displays the lowest measured pressure value (peak hold indicator). You can reset this
indicator by means of the RESET PEAKHOLD parameter.
COUNTER:T > Tmax (404)
Display
Displays the number of times the specified temperature range of the sensor has been
overshot. You can reset this counter by means of the RESET PEAKHOLD parameter.
MAX. MEAS. TEMP. (471)
Display
Displays the highest measured temperature in the sensor (peak hold indicator). You can
reset this indicator by means of the RESET PEAKHOLD parameter.
COUNTER:T < Tmin (472)
Display
Displays the number of times the specified temperature range of the sensor has been
undershot. You can reset this counter by means of the RESET PEAKHOLD parameter.
MIN. MEAS. TEMP. (474)
Display
Displays the lowest measured temperature in the sensor (peak hold indicator). You can
reset this indicator by means of the RESET PEAKHOLD parameter.
PCB COUNT:T > Tmax
(488)
Display
Displays the number of times the specified temperature range of the electronics has been
overshot.
PCB MAX. TEMP. (490)
Display
Displays the highest electronics temperature measured.
PCB COUNT:T < Tmin (492)
Display
Displays the number of times the specified temperature range of the electronics has been
undershot.
Table 29: OPERATING MENU PROCESSINFO PROCESS VALUES "Flow"
Parameter name Description