Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 187
LIN. EDIT MODE (397)
Selection
Select the entry mode for the linearization table.
Prerequisite:
TABLE SELECTION = Editor table
Options:
•Manual:
The container neither has to be filled nor emptied for this entry mode. Enter the value
pairs for the linearization table.
Semiautomatic: The container is filled or emptied in stages in this entry mode. The
device automatically records the hydrostatic pressure. The associated volume, mass or
%-value is entered.
Factory setting:
Manual
EDITOR TABLE (809)
Selection
Select table.
Prerequisite:
TABLE SELECTION = Editor table
Options:
New table:
Enter a new linearization table.
Edit measure table:
The measuring table is loaded as an editor table so that changes can be made. See
also TAB. SELECTION
Continue edit:
Edit an editor table that already exists. See also EDITOR TABLE (770)
Factory setting:
New table
EDITOR TABLE
Entry ("Semiautomatic" edit
mode)
LINE-NUMB (549)
Y-VAL. (551)
Enter table in the "Semiautomatic" editing mode.
A linearization table must have at least 2 points and may not have more than 32 points. A
point consists of LINE-NUMB, X-VAL. and Y-VAL. For this editing mode, the container is
filled or emptied in stages.
Example: Enter point for LEVEL MODE = Pressure linearized
LINE-NUMB: Confirm value displayed.
Y-VAL.: depending on the setting in the LINd. MEASURAND parameter, enter the
volume, mass or % value.
X-VAL.: The hydrostatic pressure present is displayed and saved by confirming the Y-
value.
Example: Enter point for LEVEL MODE = Height linearized
LINE-NUMB: Confirm value displayed.
Y-VAL.: depending on the setting in the COMB. MEASURAND parameter, enter the
volume, mass or % value.
X-VAL.: The hydrostatic pressure present is measured. Depending on the setting in the
COMB. MEASURAND parameter, the measured pressure is converted to a level unit
or a % and displayed. The value is saved by confirming the Y-value.
Factory setting:
LINE-NUMB = 1, X-VAL. = 0.0, Y-VAL. = 0.0
Table 18: GROUP SELECTION OPERATING MENU SETTINGS LINEARIZATION
– Local operation