Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
188 Endress+Hauser
EDITOR TABLE
Entry ("Manual" edit mode)
– LINE-NUMB (549)
– Y-VAL. (551)
–X-VAL. (550)
Enter the table in the "Manual" editing mode.
A linearization table must have at least 2 points and may not have more than 32 points. A
point consists of an index, X-value and Y-value. The container neither has to be filled nor
emptied for this editing mode.
Example: Enter point for LEVEL MODE = Pressure linearized
– LINE-NUMB: Confirm value displayed.
– X-VAL.: enter pressure value.
– Y-VAL.: depending on the setting in the LINd. MEASURAND parameter, enter the
related volume, mass or % value.
Example: Enter point for LEVEL MODE = Height linearized
– LINE-NUMB: Confirm value displayed.
– X-VAL.: The hydrostatic pressure present is measured. Depending on the setting in the
COMB. MEASURAND parameter, enter a level value or % value.
– Y-VAL.: depending on the setting in the COMB. MEASURAND parameter, enter the
related volume, mass or % value.
Factory setting:
LINE-NUMB = 1, X-VAL. = 0.0, Y-VAL. = 0.0
EDITOR TABLE (770)
Selection
Select the function for the editor table.
Options:
• Next point: enter next point.
• Last input point: skip back to previous point to correct a mistake for example.
• Accept input table: save editor table as measuring table. This overwrites the old
measuring table.
• Abort: save values entered up to this point for the editor table and display next
parameter. The editor table is not activated as a measuring table.
• Insert point: see example below.
• Delete point: the current point is deleted. See example below.
Example: Add point, in this case between the 4th and 5th point for example
– Select point 5 via the EDITOR TABLE/LINE NUMB parameter.
– Confirm current X and Y values with Enter.
– Using the EDITOR TABLE (770) parameter, select the option "Insert point".
– Point 5 is displayed for the EDITOR TABLE/LINE NUMB parameter. Enter new values
for the X-VAL and Y-VAL parameters.
Example: Delete point, in this case the 5th point for example
– Select point 5 via the EDITOR TABLE/LINE NUMB parameter.
– Using the EDITOR TABLE (770) parameter, select the option "Delete point".
– The 5th point is deleted. All of the following points are pushed up one number i.e.
following deletion, the 6th point becomes Point 5.
Factory setting:
Next point
MEASURING TABLE (549)
Display
A point of the linearization table saved (measuring table) appears on the display.
The parameter first displays the first point of the linearization table. By entering a line
number, you can directly display the corresponding point in the linearization table.
MEASURING TABLE (717)
Selection
Select the function for the measuring table.
Options:
• Next point: view next point of the measuring table.
• Last input point: view previous point of the measuring table.
• Abort: cancel measuring table display. Display next parameter.
Factory setting:
Next point
TANK DESCRIPTION (815)
Entry
Enter tank description. (max. 32 alphanumeric characters)
Factory setting:
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Table 18: GROUP SELECTION → OPERATING MENU → SETTINGS → LINEARIZATION
– Local operation
Parameter name Description