Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
192 Endress+Hauser
P01-xMx7xxxx-19-xx-xx-en-013
Fig. 54: TOTALIZER SETUP function group
*
*
*
*
*
NEG. FLOWTOT. 1
RESETTOTALIZER 1
TOTALIZER2UNIT
TOT. 2USERUNIT
FACT. U. U.TOTAL. 2
NEG. FLOWTOT. 2
MEASURED VALUE
QUICK SETUP
DISPLAYSETTINGS
POSITION ADJUSTMENT
OPERATING MENU
TOTALIZER1UNIT
TOT. 1USERUNIT
FACT. U. U.TOTAL. 1
TO
TALIZER SETUP
Flow measuring
mode only
Parameters marked with an asterisk "*"
are not always displayed.Thedisplay
depends on the settings of other parameters,
see the following Table.
Table 20: OPERATING MENU → SETTINGS → TOTALIZER SETUP
Parameter name Description
Prerequisite:
• MEASURING MODE = Flow
Note:
• See also → ä 129 ff, Section 10 "Flow measurement (via local operation and FieldCare)".
TOTALIZER 1 UNIT
(398), (662), (664), (666)
Selection
Select the unit for totalizer 1.
Depending on the setting in the FLOW-MEAS. TYPE parameter (→ ä 180) this
parameter offers a list of volume, norm volume, standard volume and mass units. When a
new volume or mass unit is selected, totalizer-specific parameters are converted and
displayed with the new unit within a unit group. When the flow mode is changed, the
totalizer value is not converted.
The index and the 3-digit ID number depends on the FLOW-MEAS. TYPE selected:
– Index 102: TOTALIZER 1 UNIT (general)
– Index 156 (398): FLOW-MEAS. TYPE "Volume operat. cond."
– Index 168 (662): FLOW-MEAS. TYPE "Mass"
– Index 170 (664): FLOW-MEAS. TYPE "Gas. std. cond."
– Index 172 (666): FLOW-MEAS. TYPE "Gas. norm cond."
Factory setting:
m
3