Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
42 Endress+Hauser
Test Read Write/
TEST_RW
Display
Index: 8
Data type: DS-85
Access: auto, OOS
This parameter is required only for the FF conformance test and has no meaning in normal
operation.
DD Resource/
DD_RESOURCE
Index: 9
Data type: visible string
Access: read only
String that indicates the tag of the resource that contains the device description for this
resource.
Manufacturer ID/
MANUFAC_ID
Display
Index: 10
Data type: unsigned16
Access: read only
Displays the manufacturer's ID number.
Endress+Hauser: 0 x 452B48 (decimal: 4533064)
Device Type/DEV_TYPE
Display
Index: 11
Data type: unsigned16
Access: read only
Displays the device ID number.
Deltabar S: hexadecimal: 1009, decimal: 4105.
Cerabar S: hexadecimal: 1007, decimal: 4103.
Deltapilot S: hexadecimal: 0 x 100B, decimal: 4107.
Device Revision/
DEV_REV
Display
Index: 12
Data type: unsigned8
Access: read only
Displays the revision number of the device.
DD Revision/DD_REV
Display
Index: 13
Data type: unsigned8
Access: read only
Displays the revision number of the device description (DD).
Grant Deny/
GRANT_DENY
Selection
Index: 14
Data type: DS-70
Access: auto, OOS
Grant or restrict access authorization for a fieldbus host system to the device. This parameter
is not evaluated by Deltabar S, Cerabar S and Deltapilot S.
Hard Types/
HARD_TYPES
Display
Index: 15
Data type: bit string
Access: read only
Displays the output signal type for the Output function blocks.
Displays the input signal type for the Input function blocks.
Resource Block