Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 43
Restart/RESTART
Selection
Index: 16
Data type: unsigned8
Access: r, w
Select the reset mode.
Options:
ENP_RESTART: A restart is needed to accept the ENP configuration changes.
Run: Standard operating mode
Resource: This mode is not supported by Endress+Hauser.
Defaults: The device data and the links of the function blocks are reset to the factory
settings. The manufacturer-specific parameters of the Transducer Block are not reset to the
factory settings.
See also Operating Instructions BA00301P (Deltabar S) or BA00302P (Cerabar S) or
BA00372P (Deltapilot S), "Factory setting" (reset) section.
Processor: Warm start of device, processor restart.
Factory: The links of the function blocks, all FF-specific and resettable manufacturer-
specific parameters are reset to the factory setting.
Features/FEATURES
Display
Index: 17
Data type: bit string
Access: read only
Displays the additional functions supported by the device. See also this Table, Feature
Selection/FEATURE_SEL parameter description.
Feature Selection/
FEATURE_SEL
Selection
Index: 18
Data type: bit string
Access: auto, OOS
Select the additional device functions. The additional functions that the device supports are
displayed in the Features/FEATURES parameter ( ä 43).
Cycle Type/
CYCLE_TYPE
Display
Index: 19
Data type: bit string
Access: read only
Displays the block execution methods supported by the device. See also this Table, Cycle
Selection/CYCLE_SEL parameter description.
Cycle Selection/
CYCLE_SEL
Display
Index: 20
Data type: bit string
Access: auto, OOS
Displays the block execution method used by the fieldbus host system. The block execution
method is selected by the fieldbus host system.
Possibilities:
Scheduled: cyclical block execution method
Block execution: sequential block execution method
Minimum Cycle Time/
MIN_CYCLE_T
Display
Index: 21
Data type: Unsigned32
Access: read only
Displays the shortest MACROCYCLE supported by the device.
Factory setting:
3200
1
/
32
ms ( 100 ms)
Memory Size/
MEMORY_SIZE
Display
Index: 22
Data type: DS-69
Access: read only
Displays the available configuration memory in kilobytes. This parameter is not supported by
Deltabar S, Cerabar S and Deltapilot S.
Nonvolatile Cycle Time/
NV_CYCLE_T
Display
Index: 23
Data type: Unsigned32
Access: read only
Displays the time interval for which the dynamic device parameters are stored in the
nonvolatile memory. Since the Cerabar S, Deltabar S and Deltapilot S units do not store the
dynamic device parameters in the nonvolatile memory, the parameter always displays the
value 0
1
/
32
ms.
Resource Block
Parameter Description

Table of Contents