Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
56 Endress+Hauser
Secondary Value/
SECONDARY_VALUE
Display
Index: 29
Data type: DS-65
Access: read only
The Secondary Value/SECONDARY_VALUE parameter is a structured parameter consisting
of two elements.
VALUE
Displays the second process value, here the sensor temperature.
STATUS
Displays the status of the second process value.
!
Note!
You can transmit the value and status of the Secondary Value/SECONDARY_VALUE
parameter via the Channel/CHANNEL parameter ( ä 96) in the Analog Input Block. The
Channel/CHANNEL must be set to "2" for this purpose.
Secondary Value Unit/
SECONDARY_VALUE_
UNIT
Selection
Index: 30
Data type: unsigned16
Access: auto, OOS
Select the unit for the second process value.
See also parameter description for Secondary Value/SECONDARY_VALUE.
Device Dialog/
DEVICE_DIALOG
Display
Index: 31
Data type: unsigned8
Access: read only
If configuration is unsuitable, this parameter displays a message indicating that a
configuration error is present. The message can also refer to the parameter that was
configured incorrectly.
Insert Pin No/SW_LOCK
Display
Index: 32
Data type: UNSIGNED16
For entering a code to lock or unlock operation.
!
Note!
The -symbol on the local operation indicates that operation is locked. Parameters
which refer to how the display appears, e.g. Language/DISPLAY_LANGUAGE and Display
Contrast/DISPLAY_CONTRAST , can still be altered.
If operation is locked by means of the DIP switch, you can only unlock operation again by
means of the DIP switch. If operation is locked by means of remote operation, you can
only unlock operation again using remote operation.
See also Operating Instructions for Deltabar S (BA00301P), Cerabar S (BA00302P) or
Deltapilot S (BA00372P), Section 5.6 "Locking/unlocking operation".
Options:
Lock: Enter a number between 0 and 9999 and 100.
Unlock: Enter the number 100.
Factory setting:
100
Status Locking/
STATUS_LOCKING
Display
Index: 33
Data type:UNSIGNED 8
Displays the current locking status of the device or conditions that can lock the device
(hardware locking, software locking).
Pressure Transducer Block
Parameter Description