Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
96 Endress+Hauser
Output Scale/
OUT_SCALE
Entry, display
Index: 11
Data type: DS-68
Access: auto, man, OOS
The Output Scale/OUT_SCALE parameter is a structured parameter consisting of four
elements.
EU_100:
Enter the upper limit for the output value of the AI Block OUT ( ä 95).
Factory setting: 100
EU_0:
Enter the lower limit for the output value of the AI Block OUT.
Factory setting: 0
UNITS_INDEX:
Select the unit.
Factory setting: %
DECIMAL:
Displays the number of places after the decimal point for the OUT output value.
Factory setting: 2
!
Note!
The OUT output value is also transmitted if it is outside the scaling range. The status
changes to BAD.
If you have selected the "Direct" option via the Linearizatin Type/L_TYPE parameter, the
settings for the Transducer Scale/XD_SCALE and Output Scale/OUT_SCALE parameters
must be identical. If this is not the case, the block goes to the OOS mode and the "Block
config error" message is displayed in the Block Error/BLOCK_ERROR parameter.
Grant Deny/
GRANT_DENY
Selection
Index: 12
Data type: DS-70
Access: auto, man, OOS
Grant or restrict access authorization for a fieldbus host system to the device. This parameter
is not evaluated by Deltabar S, Cerabar S and Deltapilot S.
I/O Options/
IO_OPTS
Selection
Index: 13
Data type: bit string
Access: OOS
Activate options for processing the input and output values of the function block.
Factory setting:
No option activated
Status Options/
STATUS_OPTS
Selection
Index: 14
Data type: bit string
Access: OOS
Specify status processing and processing of the output parameter Output/OUT.
Factory setting:
No options active
Channel/CHANNEL
Selection
Index: 15
Data type:
Access: OOS
Assign the output variables (process variables) of the "Pressure" or "Totalizer" Transducer
Blocks to an Analog Input Block as the input value.
Possibilities
1: Primary value from the Pressure Transducer Block - a pressure, level or flow value
depending on the measuring mode selected
2: Secondary value from the Pressure Transducer Block, here the sensor temperature
6: Totalizer 1 from the DP Flow Transducer Block
Factory setting:
Analog Input Block 1: Channel/CHANNEL = 1: Primary value (pressure measured value)
Analog Input Block 2: Channel/CHANNEL = 2: Secondary value (sensor temperature)
Analog Input Block 3: Channel/CHANNEL = 6: Totalizer 1
Analog Input Block
Parameter Description