Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 95
Output/OUT
Display, entry
Index: 8
Data type: DS-65
Access: auto, man, OOS
The Output/OUT parameter is a structured parameter consisting of two elements.
VALUE
Displays the output value of the Analog Input Block.
STATUS
Displays the status of the Output/OUT value.
!
Note!
The Output/OUT output value is also transmitted if it is outside the scaling range of
Output Scale/OUT_SCALE.
The unit used by the Output Scale/OUT_SCALE parameter is accepted.
If the "MAN" (manual) block mode was selected by means of the Block Mode/
MODE_BLK parameter, the output value Output/OUT and its status can be specified
manually here.
Simulation Mode/
SIMULATION_MODE
Entry, display
Index: 9
Data type: DS-82
Access: auto, man, OOS
The Simulation Mode/SIMULATION_MODE parameter is a structured parameter consisting
of five elements. As the value and status specified here run through the complete algorithm,
the behavior of the Analog Input Block can be checked.
SIMULATE_STATUS
Enter the status for simulation.
SIMULATE_STATUS
Enter the simulation value.
TRANSDUCER_STATUS
Displays the current status of the Transducer Block which is linked to the Analog Input
Block via the CHANNEL parameter.
TRANSDUCER_VALUE
Displays the current process value of the Transducer Block which is linked to the Analog
Input Block via the CHANNEL parameter.
ENABLE_DISABLE
Switch the simulation mode on and off.
!
Note!
The "Simulation" DIP switch on the electronic insert must be set to "On". See also
Operating Instructions BA00301P (Deltabar S) and BA00302P (Cerabar S) or BA00372P
(Deltapilot S), "Simulation" section.
Factory setting:
Simulation disabled (simulation mode not active)
Transducer Scale/
XD_SCALE
Entry, selection
Index: 10
Data type: DS-68
Access: man, OOS
The Transducer Scale/XD_SCALE parameter is a structured parameter consisting of four
elements.
EU_100:
Enter the upper limit for the input value of the Analog Input Block.
Factory setting: 100
EU_0:
Enter the lower limit for the input value of the Analog Input Block.
Factory setting: 0
UNITS_INDEX:
Select the unit.
Factory setting: %
DECIMAL:
Displays the number of places after the decimal point for the input value.
Factory setting: 2
!
Note!
The Transducer Scale/XD_SCALE parameter corresponds to the Primary Value Range/
PRIMARY_VALUE_RANGE parameter ( ä 53) in the Transducer Block.
If you have selected the "Direct" option via the Linearizatin Type/L_TYPE parameter, the
settings for the Transducer Scale/XD_SCALE and Output Scale/OUT_SCALE parameters
must be identical. If this is not the case, the block goes to the OOS mode and the "Block
config error" message is displayed in the Block Error/BLOCK_ERROR parameter.
Analog Input Block
Parameter Description