Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 95
Output/OUT
Display, entry
Index: 8
Data type: DS-65
Access: auto, man, OOS
The Output/OUT parameter is a structured parameter consisting of two elements.
VALUE
• Displays the output value of the Analog Input Block.
STATUS
• Displays the status of the Output/OUT value.
!
Note!
• The Output/OUT output value is also transmitted if it is outside the scaling range of
Output Scale/OUT_SCALE.
• The unit used by the Output Scale/OUT_SCALE parameter is accepted.
• If the "MAN" (manual) block mode was selected by means of the Block Mode/
MODE_BLK parameter, the output value Output/OUT and its status can be specified
manually here.
Simulation Mode/
SIMULATION_MODE
Entry, display
Index: 9
Data type: DS-82
Access: auto, man, OOS
The Simulation Mode/SIMULATION_MODE parameter is a structured parameter consisting
of five elements. As the value and status specified here run through the complete algorithm,
the behavior of the Analog Input Block can be checked.
SIMULATE_STATUS
• Enter the status for simulation.
SIMULATE_STATUS
• Enter the simulation value.
TRANSDUCER_STATUS
• Displays the current status of the Transducer Block which is linked to the Analog Input
Block via the CHANNEL parameter.
TRANSDUCER_VALUE
• Displays the current process value of the Transducer Block which is linked to the Analog
Input Block via the CHANNEL parameter.
ENABLE_DISABLE
• Switch the simulation mode on and off.
!
Note!
The "Simulation" DIP switch on the electronic insert must be set to "On". → See also
Operating Instructions BA00301P (Deltabar S) and BA00302P (Cerabar S) or BA00372P
(Deltapilot S), "Simulation" section.
Factory setting:
Simulation disabled (simulation mode not active)
Transducer Scale/
XD_SCALE
Entry, selection
Index: 10
Data type: DS-68
Access: man, OOS
The Transducer Scale/XD_SCALE parameter is a structured parameter consisting of four
elements.
EU_100:
• Enter the upper limit for the input value of the Analog Input Block.
• Factory setting: 100
EU_0:
• Enter the lower limit for the input value of the Analog Input Block.
• Factory setting: 0
UNITS_INDEX:
• Select the unit.
• Factory setting: %
DECIMAL:
• Displays the number of places after the decimal point for the input value.
• Factory setting: 2
!
Note!
• The Transducer Scale/XD_SCALE parameter corresponds to the Primary Value Range/
PRIMARY_VALUE_RANGE parameter (→ ä 53) in the Transducer Block.
• If you have selected the "Direct" option via the Linearizatin Type/L_TYPE parameter, the
settings for the Transducer Scale/XD_SCALE and Output Scale/OUT_SCALE parameters
must be identical. If this is not the case, the block goes to the OOS mode and the "Block
config error" message is displayed in the Block Error/BLOCK_ERROR parameter.