Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
68 Endress+Hauser
Tank Volume/
TANK_VOLUME
Entry
Index: 64
Data type: float
Access: auto, OOS
Enter the tank volume.
Prerequisite:
• Lin. Measurand/LINEAR_MEASURAND = Volume,
Calibration Mode/CALIBRATION_MODE = Dry
• Lin. Measurand/LINEAR_MEASURAND = Mass,
Calibration Mode/CALIBRATION_MODE = Dry
– Lin. Measurand = LINEAR_MEASURAND
– Calibration Mode = CALIBRATION_MODE
Factory setting:
1.0 m
3
Tank Height/
TANK HEIGHT
Entry
Index: 65
Data type: float
Access: auto, OOS
Enter the tank height.
Prerequisite:
• Lin. Measurand/LINEAR_MEASURAND = Volume,
Calibration Mode/CALIBRATION_MODE = Dry
• Lin. Measurand/LINEAR_MEASURAND = Mass,
Calibration Mode/CALIBRATION_MODE = Dry
– Lin. MeasurandD = LINEAR_MEASURAND
– Calibration Mode = CALIBRATION_MODE
Factory setting:
1.0 m
100% Point/HUNDRED_
PERCENT_VALUE
Entry
Index: 66
Data type: float
Access: auto, OOS
Enter the level value for the 100% point.
Prerequisite:
• Comb. Measurand/COMBINED_MEASURAND = %-height and volume,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = %-height and mass,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = %-height + %,
Calibration Mode/CALIBRATION_MODE = Dry
– Comb. Measurand = COMBINED_MEASURAND
– Calibration Mode = CALIBRATION_MODE
Example:
– The 100 %-point should correspond to 4 m.
– Select the "m" unit via the Height Unit/HEIGHT_UNIT parameter.
– Enter the value "4" for this 100% Point/HUNDRED_PERCENT_VALUEparameter.
Factory setting:
1.0
Level Min/LEVEL_MIN
Entry
Index: 67
Data type: float
Access: auto, OOS
Enter the minimum level to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum level to be expected, the more accurate
the measurement result.
Factory setting:
0.0
Level Max/LEVEL_MAX
Entry
Index: 68
Data type: float
Access: auto, OOS
Enter the maximum level to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the maximum level to be expected, the more
accurate the measurement result.
Factory setting:
100.0
Process Density/
PROCESS_DENSITY
Entry
Index: 69
Data type: float
Access: auto, OOS
Enter a new density value for density correction.
The calibration was carried out with the medium water, for example. Now the container is to
be used for another fluid with another density. The calibration is corrected appropriately by
entering the new density value in the Process Density/PROCESS_DENSITY parameter.
Factory setting:
1.0
Pressure Transducer Block
Parameter Description