Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 69
Table Selection/
LINEARIZATION_
TABLE_SELECTION
Index: 70
Data type: UNSIGNED8
Access: auto, OOS
Select table.
The device works with a measuring and an editor table. The measuring table is used to
calculate the measured value. To make sure measuring also runs properly when entering a
new table, there is another table, the editor table, for entering new values.
Options:
•View meas. table
•Editor table
Factory setting:
View meas. table
Lin. Edit Mode/
LINEARIZATION_
EDIT_MODE
Entry
Index: 71
Data type: unsigned8
Access: auto, OOS
Select the entry mode for the linearization table.
Options:
Manual: The container neither has to be filled nor emptied for this entry mode. Enter the
value pairs for the linearization table.
Semiautomatic: The container is filled or emptied in stages in this entry mode. The device
automatically records the hydrostatic pressure. The associated volume, mass or %-value is
entered.
Factory setting:
Manual
Editor Table/
LINEARIZATION_
TABLE_PRE_EDIT
Index: 72
Data type: UNSIGNED8
Access: auto, OOS
Select table.
Prerequisite:
Table Selection/LINEARIZATION_TABLE_SELECTION = Editor table
Options:
New table:
Enter a new linearization table.
Edit measure table:
The measuring table is loaded as an editor table so that changes can be made.
Siehe also TAB. SELECTION.
Continue edit:
Edit an editor table that already exists.
See also EDITOR TABLE (770).
Factory setting:
New table
Line-Numb/
LINEARIZATION_
TABLE_INDEX
Index: 73
Data type: UNSIGNED8
Access: auto, OOS
Enter the line number for the linearization table. A linearization table must have at least
2 points and may not have more than 32 points.
Table Selection/LINEARIZATION_TABLE_SELECTION = View meas. table
Via this parameter you can select the point of the linearization table which should be
displayed.
Table Selection/LINEARIZATION_TABLE_SELECTION = Editor table
Enter a point via the Line-Numb/LINEARIZATION_TABLE_INDEX, X-Val/
LINEARIZATION_TABLE_X_VALUE and Y-Val/LINEARIZATION_TABLE_Y_VALUE
parameters.
See also this table, parameter descriptions for Lin. Edit Mode/LINEARIZATION_EDIT_
MODE, X-Val/LINEARIZATION_TABLE_X_VALUE ("Manual" entry mode),
X-Val/LINEARIZATION_TABLE_X_VALUE ("Semiautomatic" entry mode) and
Y-Val/LINEARIZATION_TABLE_Y_VALUE.
!
Note!
In the operating program, you can enter a complete linearization table in one go, and view
it, via the "Lin.-Tab." window.
X-Val/LINEARIZATION_
TABLE_X_VALUE
(manual)
Index: 74
Data type: float
Access: auto, OOS
Enter the pressure value for the linearization table.
See also Lin. Edit Mode/LINEARIZATION_EDIT_MODE, Line-Numb/
LINEARIZATION_TABLE_INDEX and Y-Val/LINEARIZATION_TABLE_Y_VALUE.
Prerequisite:
Table Selection/LINEARIZATION_TABLE_SELECTION = Editor table
Pressure Transducer Block
Parameter Description