Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
70 Endress+Hauser
X-Val/LINEARIZATION_
TABLE_X_VALUE
(semiautomatic)
Index: 74
Data type: float
Access: auto, OOS
In the "Semiautomatic" entry mode, the container is filled or emptied in stages.
The X-Val/LINEARIZATION_TABLE_X_VALUE displays the measured hydrostatic pressure.
Prerequisite:
Table Selection/LINEARIZATION_TABLE_SELECTION = Editor table
Operating program
The X-Val/LINEARIZATION_TABLE_X_VALUE is saved by confirming the Y-value.
HARD handheld
Confirm X-Val/LINEARIZATION_TABLE_X_VALUE displayed.
See also Lin. Edit Mode/LINEARIZATION_EDIT_MODE, Line-Numb/
LINEARIZATION_TABLE_INDEX and Y-Val/LINEARIZATION_TABLE_Y_VALUE.
Y-Val/LINEARIZATION_
TABLE_Y_VALUE
Index: 75
Data type: float
Access: auto, OOS
Enter the volume, mass or %-value belonging to the X-Val/LINEARIZATION_TABLE_X_
VALUE for the linearization table.
Prerequisite:
Table Selection/LINEARIZATION_TABLE_SELECTION = Editor table
Depending on the setting in the Lind. Measurand/LINEARIZED_MEASURAND or Comb.
Measurand/COMBINED_MEASURAND parameters, enter a volume, mass or %-value here.
See also table, parameter description for Lin. Edit Mode/LINEARIZATION_EDIT_MODE,
Line-Numb/LINEARIZATION_TABLE_INDEX, X-Val/LINEARIZATION_TABLE_
X_VALUE ("Manual" entry mode), X-Val/LINEARIZATION_TABLE_X_VALUE
("Semiautomatic" entry mode)
Editor Table/
LINEARIZATION_
TABLE_POST_EDIT
Index: 76
Data type: UNSIGNED8
Access: OOS
Select the function for the editor table.
Options:
Next point: no function
Last input point: no function
Accept input table: save editor table as measuring table. This overwrites the old measuring
table.
Abort: save values entered up to this point for the editor table and display next parameter.
The editor table is not activated as a measuring table.
Insert point: see example below.
Delete point: the current point is deleted. See example below.
Example: Add point, in this case between the 4th and 5th point for example
Select Point 5 via the Line-Numb/LINEARIZATION_TABLE_INDEX parameter.
Using the Editor Table/LINEARIZATION_TABLE_POST_EDIT parameter, select the
"Insert point" option.
Point 5 is displayed for the Line-Numb/LINEARIZATION_TABLE_INDEX parameter.
Enter new values for the X-Val/LINEARIZATION_TABLE_X_VALUE and
Y-Val/LINEARIZATION_TABLE_Y_VALUE parameters.
Example: Delete point, in this case the 5th point for example
Select Point 5 via the Line-Numb/LINEARIZATION_TABLE_INDEX parameter.
Using the Editor Table/LINEARIZATION_TABLE_POST_EDIT parameter, select the
"Delete point" option.
The 5th point is deleted. All of the following points are pushed up one number i.e.
following deletion, the 6th point becomes Point 5.
Factory setting:
Next point
Measuring Table/
LINEARIZATION_TABLE
_POST_VIEW
Index: 77
Data type: UNSIGNED8
Access: auto, OOS
Select the function for the measuring table.
Options:
Next point: view next point of the measuring table.
Last input point: view previous point of the measuring table.
Abort: cancel measuring table display. Display next parameter.
Factory setting:
Next point
Tank Description/
LEVEL_TANK_
DESCRIPTION
Entry
Index: 78
Data type: visible string
Access: auto, OOS
Enter tank description. (max. 32 alphanumeric characters)
Factory setting:
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Pressure Transducer Block
Parameter Description