Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 71
Sensor Pressure/
SENSOR_PRESSURE
Display
Index: 79
Data type: float
Access: auto, OOS
Displays the measured pressure before sensor trim, position adjustment and damping. → See
also the following graphic, parameter description for Pressure/PRESSURE.
Pressure/PRESSURE
Display
Index: 80
Data type: float
Access: auto, OOS
Displays the measured pressure after sensor trim, position adjustment and damping. This
value corresponds to the Primary Value/PRIMARY_VALUE parameter in the "Pressure"
measuring mode.
P01-xMD7xxxx-05-xx-xx-en-011
Level Before Lin/
LEVEL_BEFORE_
LINEARISATION
Display
Index: 81
Data type: float
Access: auto, OOS
Displays the level value prior to linearization.
Prerequisite:
• Level Mode/LEVEL_MODE = Linear or height linearized
Depending on the setting for the Lin. Measurand/LINEAR_MEASURAND or Comb.
Measurand/COMBINED_MEASURAND parameter, this parameter displays the current level
in % or in a unit of level.
Sensor Meas. Type/
SENSOR_MEAS_TYPE
Display
Index: 82
Data type: unsigned16
Access: read only
Displays the sensor type.
• Deltabar S = Differential
• Cerabar S with gauge pressure sensors = Relative
• Cerabar S with absolute pressure sensors = Absolute
• Deltapilot S with gauge pressure sensors = Relative
Pressure Transducer Block
Parameter Description
P
PV
Sensor
Analog
Input
Block
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim
Transducer Block
PRESSURE_1_
AFTER_DAMPING/
PRESSURE
PRESSURE_1_
AFTER_CALIBRATION/
CORRECTED PRESS.
PRESSURE_1_
AFTER_SENSOR/
SENSOR PRESSURE