Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 89
7.3.6 Diagnostic Transducer Block
Display Contrast/
DISPLAY_CONTRAST
Entry
Index: 14
Data type: unsigned8
Access: auto, OOS
Adjust contrast of local operation.
You specify the contrast of the display with a number.
Input range:
4 to 13, 4: contrast weaker (brighter), 13: contrast stronger (darker).
Factory setting:
8
Language/
DISPLAY_LANGUAGE
Selection
Index: 15
Data type: unsigned8
Access: auto, OOS
Select the menu language for the local operation.
Options:
English
•Deutsch
Français
•Español
Katakana
Chinese
Factory setting:
English
Digits Set/
SIL_DIGITS_TEST_
STRING
Display
Index: 16
Data type: visible string
Access: read only
This parameter is used to check whether characters and digits are displayed correctly on the
local operation. "0123456789.-" is shown if the units are displayed correctly.
Diagnostic Transducer Block
Parameter Description
Insert Pin No/SW_LOCK
Index: 11
Data type: unsigned16
Access: OOS
For entering a code to lock or unlock operation.
!
Note!
The -symbol on the local operation indicates that operation is locked. Parameters
which refer to how the display appears, e.g. Language/DISPLAY_LANGUAGE and Display
Contrast/DISPLAY_CONTRAST, can still be altered.
If operation is locked by means of the DIP switch, you can only unlock operation again by
means of the DIP switch. If operation is locked by means of remote operation, you can
only unlock operation again using remote operation.
See also Operating Instructions for Deltabar S (BA00301P), Cerabar S (BA00302P) or
Deltapilot S (BA00372P), Section 5.6 "Locking/unlocking operation".
Options:
Lock: Enter a number between 0 and 9999 and 100 i.
Unlock: Enter the number 100.
Factory setting:
100
Status Locking/
STATUS_LOCKING
Index: 12
Data type: unsigned8
Access: OOS
Displays the current locking status of the device or conditions that can lock the device
(hardware locking, software locking).
Display Transducer Block