Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
90 Endress+Hauser
Simulation Mode/
SIMULATION_MODE
Selection
Index: 13
Data type: unsigned8
Access: auto, OOS
Switch on simulation and select simulation type.
Any simulation running is switched off if the measuring mode or level mode is changed.
Options:
•None
• Pressure
• Flow (only differential pressure transmitter)
• Level
• Tank content
• Alarm/warning
P01-xMD7xxxx-05-xx-xx-en-004
Factory setting:
None
Units Index/
SCALE_OUT_UNITS_
INDEX
Display
Index: 14
Data type: unsigned16
Access: read only
Displays the unit selected via the Scale Out/SCALE_OUT parameter (→ ä 58) in the
Pressure Transducer Block.
Simulated Value/
SIMULATED_VALUE
Entry
Index: 15
Data type: float
Access: auto, OOS
Enter the simulation value.
Prerequisite:
• Simulation Mode/SIMULATION_MODE = Pressure, flow, level or tank content.
Sim. Error No./
SIMULATION_ERROR_
NUMBER
Entry
Index: 16
Data type: unsigned16
Access: auto, OOS
Enter the message number for simulation.
→ See also these Operating Instructions, Section 12.1 "Messages", "Code" table column.
Prerequisite:
• Simulation Mode/SIMULATION_MODE = Alarm/warning
Factory setting:
613 (simulation active)
Alarm Status/
ALARM_STATUS
Display
Index: 17
Data type: unsigned16
Access: read only
Displays the current messages present. If two or more messages are present, the message
with the highest priority is shown on the display. → See also these Operating Instructions,
Section 12.1 "Messages" and Section 12.3 "Confirming messages".
Last Diag. Code/
LAST_DIAGNOSTIC_
CODE
Display
Index: 18
Data type: unsigned16
Access: read only
Displays the last error that occurred and was eliminated.
!
Note!
• The message displayed here can be deleted by means of the Reset All Alarms/RESET_
ALL_ALARMS parameter.
Diagnostic Transducer Block
Parameter Description
P
PV
Simulation value pressure
Transducer Block
– Simulation value level
– Simulation value tank content
Simulationvalue flow
Sensor
Analog
Input
Block
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim