6.3 Minimum/maximum fail-safe mode
Function By using the minimum/maximum fail-safe switching feature, the FEC 22 can be used
in all applications where a fail-safe function is required.
Setting
Procedure
• Turn the rotary switch to
Position 5.
• When first delivered or
after a reset the extreme
right LED in the chain
lights up:
maximum
fail-safe activated.
• Minimum and maximum
fail-safe mode can be
toggled by pressing the
left key.
• The setting can be read
off on the LED chain.
6.4 Switching delay
This function enables the switching delay time to be altered (factory-set value = 1.5 s)
so that the electronic insert can switch accordingly when the probe is covered or
uncovered.
Minimum fail-safe Maximum fail-safe
DC-PNP AC-DPDT Red LED DC-PNP AC-DPDT Red LED
Probe
covered
connected
relays energised blocked relays de-energised
Probe
uncovered
blocked relays de-energised
connected
relays energised
Power supply
failure
blocked
relays de-energised
blocked
relays de-energised
Table 6.1