6.3 Minimum/maximum fail-safe mode
Function By using the minimum/maximum fail-safe switching feature, the FEC 22 can be used
in all applications where a fail-safe function is required.
Setting
Procedure
Turn the rotary switch to
Position 5.
When first delivered or
after a reset the extreme
right LED in the chain
lights up:
maximum
fail-safe activated.
Minimum and maximum
fail-safe mode can be
toggled by pressing the
left key.
The setting can be read
off on the LED chain.
6.4 Switching delay
This function enables the switching delay time to be altered (factory-set value = 1.5 s)
so that the electronic insert can switch accordingly when the probe is covered or
uncovered.
Minimum fail-safe Maximum fail-safe
DC-PNP AC-DPDT Red LED DC-PNP AC-DPDT Red LED
Probe
covered
connected
relays energised blocked relays de-energised
Probe
uncovered
blocked relays de-energised
connected
relays energised
Power supply
failure
blocked
relays de-energised
blocked
relays de-energised
Table 6.1
1(+)
3
1 2 3 7 8 9
3
1(+)
1 2 3
7 8 9
3
1(+)
1 2 3
7 8 9
1(+)
3
1 2 3 7 8 9
U0V
3
1(+)
1 2 3
7 8 9
3
1(+)
1 2 3
7 8 9
1
3
7
MAXMIN
MAX
MAX
MIN
MIN
1x
2x
0x
7
3
1
MIN
MAX
MIN
MAX
BA160Y66
Fig. 6.4
Minimum/maximum fail-safe
6 Additional Settings Elektronic insert FEC 22
36 Endress+Hauser