Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Operating menu
Endress+Hauser 213
Value 1 to 4 display
Navigation  Setup → Advanced setup → Display → Value 1 display
Description Select the measured value that is shown on the local display.
Selection • None
12)
• Level linearized
• Distance
• Interface linearized
• Interface distance
• Thickness upper layer
• Current output 1
13)
• Measured current
• Current output 2
• Terminal voltage
• Electronic temperature
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Factory setting For level measurements
• Value 1 display: Level linearized
• Value 2 display: Distance
• Value 3 display: Current output 1
• Value 4 display: None
For interface measurements and one current output
• Value 1 display: Interface linearized
• Value 2 display: Level linearized
• Value 3 display: Thickness upper layer
• Value 4 display: Current output 1
For interface measurements and two current outputs
• Value 1 display: Interface linearized
• Value 2 display: Level linearized
• Value 3 display: Current output 1
• Value 4 display: Current output 2
Decimal places 1 to 4
Navigation  Setup → Advanced setup → Display → Decimal places 1
Description Select the number of decimal places for the display value.
Selection • x
• x.x
• x.xx
• x.xxx
• x.xxxx
Factory setting x.xx
12) can not be selected for the 'Value 1 display" parameter.
13) Visibility depends on order options or device settings