Levelflex FMP50/51/52/53/54/55/56/57 XA00634F-A
8 Endress+Hauser
Connection data Basic specification, Position 1, 2 (Approval) = NA, NB
Ex ia
Power supply and signal circuit with protection type: intrinsic safety Ex ia IIC or IIB.
Service interface (CDI)
Taking the following values into consideration, the device can be connected to the Endress+Hauser FXA291
service tool or a similar interface:
Basic specification, Position 3 (Power Supply; Output) = A TRC [01]
Terminal 1 (+), 2 (–)
Power supply:
U
i
= 30 V
I
i
= 300 mA
P
i
= 1 W
effective inner inductance L
i
= 0 μH
effective inner capacitance C
i
= 12 nF
Basic specification, Position 3 (Power Supply; Output) = C TRC [04]
Terminal 1 (+), 2 (–) Terminal 3 (+), 4 (–)
Power supply: Output 4...20 mA:
U
i
= 30 V
I
i
= 300 mA
P
i
= 1 W
U
i
= 30 V
I
i
= 300 mA
P
i
= 1 W
U
o
= 0 V
effective inner inductance L
i
= 0 μH
effective inner capacitance C
i
= 30 nF
effective inner inductance L
i
= 0 μH
effective inner capacitance C
i
= 30 nF
Service interface
U
i
= 7.3 V
effective inner inductance L
i
= negligible
effective inner capacitance C
i
= negligible
U
o
= 7.3 V
I
o
= 100 mA
P
o
= 160 mW
permitted outer inductance L
o
= negligible
permitted outer capacitance C
o
= negligible

Other manuals for Endress+Hauser Levelflex FMP54