Commissioning (via operating menu) Levelflex FMP55 HART
58 Endress+Hauser
8.5 Configuration of an interface measurement
D
L
L
L
F
L
I
UP
D
I
LN
E
R
0%
100%
DK (DC )
2 2
DK DC
1 1
( )
A0011177
17 Configuration parameters for interface measurements
R = Reference pioint of the measurement D
I
= Interface distance (Distance from reference point to lower medium)
E = Empty calibration (= zero point) L
I
= Interface
F = Full calibration (= span) D
L
= Distance
LN = Length of probe L
L
= Level
UP = Measured thickness upper layer
1. Setup → Device tag
Enter tag for measuring point.
2. Setup → Operating mode
Select the Interface with capacitance option
3. Setup → Distance unit
Select distance unit.
4. Setup → Tank type
Select tank type.
5. Setup → Tube diameter (only if "Tank type" = "Bypass / pipe")
Enter the diameter of the bypass or stilling well.
6. Setup → DC value
Enter dielectric constant of the upper medium.