Functional Safety Manual
for the Memosens transmitter Liquiline M CM42 SIL
Version: Page:
2.0
17 of 72
e vorbehalten. Das Kopieren dieses Dokuments und die Verwendung von Teilen aus diesem Dokument ist
ohne schriftliche Genehmigung der Endress+Hauser Conducta GmbH+Co. KG nicht erlaubt.
All rights reserved. Passing on and copying of this document, use and communication of its contents not
permitted without written authorization from Endress+Hauser Conducta GmbH+Co. KG.
This is the safe function block F_1oo2AI of a Siemens PLC:
This function block checks for valid inputs, compares the two inputs against a
configured delta tolerance and checks for a discrepancy time. See the manuals of the
used PCS for more information. The allowed deviation is set to "DELTA" = 1mA and
"DIS_TIME" = 1second.